Instructions for the driver of the boiler room fireman. Employment contract with the boiler room fireman

We bring to your attention a typical example of a job description for a fireman of industrial furnaces, sample 2017. A person with special training may be appointed to this position. Don’t forget, each instruction for a fireman of industrial furnaces is handed out against a signature.

Typical information about the knowledge that a stoker in industrial furnaces must have is presented. About duties, rights and responsibilities.

This material is part of the huge library of our website, which is updated daily.

1. General provisions

1. The fireman of industrial furnaces belongs to the category of workers.

2. A person with special training is hired for the position of fireman of industrial furnaces, without presenting requirements for education and work experience, with the assignment of the following categories:

when servicing up to 2 production furnaces with a stationary hearth or up to 2 conveyor furnaces with production bakery products each shift up to 3 tons, working at gaseous fuel— 2nd category;

when servicing 3 or more production ovens with a stationary hearth or 3 or more conveyor ovens with a bakery product output of up to 3 tons each per shift, or up to 2 conveyor ovens with a bakery product output of more than 3 to 10 tons each per shift , or one drying chamber operating on gaseous fuel - 3rd category;

when servicing 3 or more conveyor ovens with the production of bakery products each per shift over 3 to 10 tons, or one or more conveyor ovens with the production of bakery products each per shift more than 10 tons, or 2 or more drying chambers operating on gaseous fuel - 4th category.

3. A fireman of industrial furnaces is hired and dismissed by the director of the organization upon the recommendation of _____________.

4. The fireman of industrial furnaces must know:

a) special (professional) knowledge for the position:

— processes occurring during fuel combustion;

— basics of the technological process for the production of bakery products;

— types, grades and calorie content of fuel;

— methods and rules of combustion various types fuel and methods of its economical consumption;

— duration of baking of the produced varieties of bakery products;

- procedure for moistening the baking chamber;

— design, principle of operation and operating rules of maintained furnaces and used control and measuring instruments;

b) general knowledge of an employee of the organization:

— rules and regulations of labor protection, safety precautions, industrial sanitation and fire protection,

— rules for using funds personal protection;

— requirements for the quality of work (services) performed and for the rational organization of labor in the workplace;

— types of defects and ways to prevent and eliminate them;

— production alarm.

5. In his activities, the fireman of industrial furnaces is guided by:

- legislation of the Russian Federation,

- Charter of the organization,

- orders and instructions director of the organization,

- this job description,

— Internal labor regulations of the organization.

6. The fireman of industrial furnaces reports directly to ____________ worker with higher qualifications, the head of production (site, workshop) and the director of the organization

7. During the absence of a fireman of industrial furnaces (business trip, vacation, illness, etc.), his duties are performed by a person appointed by the director of the organization on the proposal of the head of production (site, workshop) in the prescribed manner, who acquires the corresponding rights, duties and is responsible for the performance duties assigned to him.

2. Job responsibilities of a fireman for industrial furnaces

The job responsibilities of a fireman for industrial furnaces are:

a) Special (professional) job responsibilities:

— Conducting the process of fuel combustion in the furnaces of industrial furnaces operating on solid, liquid and gaseous fuels.

— Checking the serviceability of the furnace system and instrumentation.

— Regulation of the fuel combustion process, draft, temperature conditions established for each type of bakery product.

— Control of the combustion process and fuel consumption.

— Cleaning of fireboxes.

— Removal of slag and ash.

— Delivery of fuel, transportation of slag and ash.

b) General job responsibilities of an employee of the organization:

— Compliance with the internal labor regulations and other local regulations of the organization, internal rules and regulations of labor protection, safety precautions, industrial sanitation and fire protection.

— Fulfillment, within the framework of the employment contract, of the orders of the employees to whom it was repaired in accordance with these instructions.

— Carrying out work on acceptance and delivery of shifts, cleaning and washing, disinfection of serviced equipment and communications, cleaning of the workplace, devices, tools, as well as maintaining them in proper condition.

— Maintaining established technical documentation.

3. Rights of the stoker of industrial furnaces

The stoker of industrial furnaces has the right:

1. Submit proposals for management’s consideration:

— to improve work related to those provided for herein instructions and duties,

— on bringing to material and disciplinary liability employees who violated production and labor discipline.

2. Request from structural divisions and employees of the organization the information necessary for him to fulfill his job responsibilities.

3. Get acquainted with the documents defining his rights and responsibilities for his position, criteria for assessing the quality of performance of official duties.

4. Get acquainted with the draft decisions of the organization’s management relating to its activities.

5. Require the management of the organization to provide assistance, including ensuring organizational and technical conditions and execution of the established documents necessary for the performance of official duties.

6. Other rights established by current labor legislation.

4. Responsibility of the fireman of industrial furnaces

The fireman of industrial furnaces is responsible in the following cases:

1. For improper performance or failure to fulfill one’s job duties provided for in this job description - within the limits established by the labor legislation of the Russian Federation.

2. For offenses committed in the course of their activities - within the limits established by the current administrative, criminal and civil legislation of the Russian Federation.

3. For causing material damage to the organization - within the limits established by the current labor and civil legislation of the Russian Federation.

Job Description stokers for industrial furnaces - 2017 model. Job responsibilities of a fireman of industrial furnaces, rights of a fireman of industrial furnaces, responsibility of a fireman of industrial furnaces.

JOB DESCRIPTION

STOKER BOILER ROOM

I. General provisions

1. The boiler room stoker belongs to the category of workers.

2. The boiler room fireman is appointed to the position and dismissed by order of the school director.

3. A boiler room fireman is guided in his work activities by:
- regulations, as well as instructions and methodological recommendations regulating activities in the field of maintenance and operation of boiler houses and boiler house equipment;
- school charter;
- internal labor regulations;
- orders and instructions of the school director;
- this job description.

4. A boiler room stoker must know:
- design and principle of operation of solid fuel and electric hot water boilers;
- operational data of boiler equipment and mechanisms;
- arrangement of automatic control devices;
- rules for maintaining the operating mode of the boiler room depending on instrument readings;
- diagrams of pipeline networks and alarms in the boiler room;
- rules for setting up and regulating instrumentation;
- rules and regulations of labor protection, safety and fire protection.

5. The boiler room fireman reports directly to the school director.

6. During the absence of the boiler room stoker (illness, vacation, etc.), his duties are performed by a person appointed in the prescribed manner, who bears full responsibility for their proper performance.

II. Job responsibilities

1. Serves solid fuel and electric water heating boilers.

2. Switches supply lines.

3. Monitors the coolant level in the heating system.

4. Turns on and off automatic boiler power supply equipment.

5. Conducts preventive inspections of boilers, their auxiliary mechanisms, control and measuring instruments and participates in scheduled preventive maintenance of boiler units.

6. Accepts boilers and their auxiliary mechanisms from repair and prepares them for operation.

III. Rights


The boiler room stoker has the right:

1. For all social guarantees provided for by law.

2. Require the management of the enterprise to provide assistance in the performance of their official duties and the exercise of rights.

3. Require the creation of conditions for execution official duties, including providing necessary equipment, inventory.

4. Get acquainted with the draft decisions of the enterprise management concerning its activities.

5. Submit proposals for improvement of the organization and methods of work performed by the enterprise management for consideration.

6. Request personally or on behalf of your immediate supervisor documents necessary to perform your job duties.

7. Improve your professional qualifications.

IV. Responsibility


The boiler room fireman is responsible for:

1. Failure to perform or improper performance of one’s job duties as provided for in this job description - within the limits determined by the current labor legislation.

2. Causing material damage - within the limits determined by current labor and civil legislation.

3. Offenses committed in the course of carrying out their activities - within the limits determined by the current administrative, criminal and civil legislation.

JOB DESCRIPTION FOR BOILER ROOM STOKER

I. General provisions

  1. The boiler room stoker belongs to the category of workers.
  2. A boiler room fireman is appointed to the position and dismissed from it by order of _____________________ upon the recommendation of _____________________.
  3. A person with secondary education is appointed to the position of boiler room stoker. vocational education without any work experience requirements.
  4. A boiler room fireman is guided in his work activities by:
    - regulations, as well as instructions and methodological recommendations regulating activities in the field of maintenance and operation of boiler houses and boiler house equipment;
    - the charter of the enterprise;
    - internal labor regulations;
    - orders and instructions from the immediate supervisor;
    - this job description.
  5. A boiler room stoker must know:
    - design and principle of operation of water heating and steam boilers of various systems;
    - operational data of boiler equipment and mechanisms;
    - arrangement of automatic control devices;
    - rules for maintaining the operating mode of the boiler room depending on instrument readings;
    - diagrams of pipeline networks and alarms in the boiler room;
    - rules for setting up and regulating instrumentation;
    - rules and regulations of labor protection, safety and fire protection.
  6. The boiler room fireman reports directly to _________________________________.
  7. During the absence of the boiler room stoker (illness, vacation, etc.), his duties are performed by a person appointed in the prescribed manner, who bears full responsibility for their proper performance.
  8. _________________________________________________________________.

II. Job responsibilities

  1. Serves hot water and steam boilers with a total heating capacity of over 84 to 273 GJ/h (over 20 to 65 Gcal/h) or serves in the boiler room individual hot water and steam boilers with a boiler heating capacity of over 273 to 546 GJ/h (over 65 to 130 Gcal/h), operating on solid fuel.
  2. Switches supply lines.
  3. Fills and drains steam lines.
  4. Turns on and off automatic boiler power supply equipment.
  5. Conducts preventive inspections of boilers, their auxiliary mechanisms, control and measuring instruments and participates in scheduled preventive maintenance of boiler units.
  6. Accepts boilers and their auxiliary mechanisms from repair and prepares them for operation.
  7. _________________________________________________________________.
  8. _________________________________________________________________.

III. Rights


The boiler room stoker has the right:
  1. For all social guarantees provided for by law.
  2. Require the management of the enterprise to provide assistance in the performance of their official duties and the exercise of rights.
  3. Require the creation of conditions for the performance of official duties, including the provision of the necessary equipment and inventory.
  4. Get acquainted with the draft decisions of the enterprise management concerning its activities.
  5. Submit proposals for improvement of the organization and methods of work performed by the enterprise management for consideration.
  6. Request personally or on behalf of your immediate supervisor documents necessary to perform your job duties.
  7. Improve your professional qualifications.
  8. _________________________________________________________________.
  9. _________________________________________________________________.

IV. Responsibility


The boiler room fireman is responsible for:
  1. Failure to perform or improper performance of one’s job duties as provided for in this job description - within the limits determined by the current labor legislation.
  2. Causing material damage - within the limits determined by current labor and civil legislation.
  3. Offenses committed in the course of carrying out their activities - within the limits determined by the current administrative, criminal, and civil legislation.
  4. _________________________________________________________________.
  5. _________________________________________________________________.

____________________________________________ (instruction number or other details)

GENERAL OCCUPATIONAL SAFETY REQUIREMENTS

1. Persons at least 18 years of age who have undergone a medical examination, training and certification, instruction, internship and testing of knowledge on labor safety issues and who have a certificate for the right to service boilers are allowed to work as a driver (fireman) of a boiler room.
2. The driver (stoker) of the boiler room is obliged to:
comply with the rules of behavior on the territory of the organization, in production, auxiliary and household premises, work and rest hours, labor discipline (resting and smoking is allowed only in specially equipped places for this purpose). It is not allowed to appear at work in a state of alcoholic intoxication or in a state caused by the use of narcotic, psychotropic, toxic and other intoxicating substances, as well as to drink alcoholic beverages, use narcotic, psychotropic, toxic and other intoxicating substances in working hours or at the place of work;
while in the territory, in production premises comply with the requirements of posters and safety signs, adequately respond to warning light and sound signals, move only along specially established service passage routes;
comply with labor protection, industrial and fire safety, know the procedure for action in case of fire and the telephone numbers for calling emergency departments, the location of fire extinguishing equipment and be able to use them;
fulfill the standards and obligations on labor protection provided for by the collective agreement, employment contract, internal labor regulations;
be able to promptly identify problems in the operation of boilers, auxiliary equipment, pipelines, fittings, fittings, and if problems are detected, immediately eliminate them;
be able to check the proper operation of water indicating devices, pressure gauges, safety devices, alarms, check valves and other technical devices;
correctly use the personal protective equipment provided to him, and in the event of their absence or malfunction, immediately notify his immediate supervisor;
provide assistance and cooperate with the employer in ensuring healthy and safe working conditions, immediately notify your immediate supervisor or other official of the employer about the malfunction of equipment, tools, devices, vehicles, protective equipment, or about a deterioration in your health;
immediately report to the immediate supervisor about any situation that threatens the life or health of workers and others, an accident that occurred at work, and provide assistance officials the employer in taking measures to provide the necessary assistance to victims and delivering them to a health care organization;
know the location of the first aid kit medical care, be able to use the medicines and medical products contained in it and be able to provide first aid to victims in industrial accidents;
perform only the work that is assigned to him, the safe methods of performing which are known; in case of any questions related to the safe performance of work, contact your immediate supervisor;
don't leave workplace during working hours without the permission of the immediate supervisor;
know and observe the rules of personal hygiene: wash your hands with soap or similar detergents before eating or smoking, do not use flammable and combustible liquids (gasoline, kerosene, acetone, etc.) for these purposes. For drinking, it is necessary to use water from devices specially designed for this purpose (saturators, drinking tanks, fountains, etc.);
store personal protective equipment and personal clothing in designated places;
perform other duties provided for by labor protection legislation.
3. Dangerous and harmful production factors that can affect the driver (fireman) of the boiler room in the process of performing work are:
moving vehicles and mechanisms; moving parts of production equipment; collapsing structures;
objects falling from a height;
increased gas and dust levels in the air in the working area;
increased temperature of the heated surfaces of the boiler, steam pipelines and hot water;
increased or decreased air temperature in the working area;
increased voltage value in electrical circuit, the closure of which can occur through the human body;
fire and explosion hazards;
insufficient illumination of the work area;
sharp edges, burrs and roughness on surfaces solid fuel, tools and equipment;
physical overload.
4. The driver (stoker) of the boiler room is provided with personal protective equipment according to standard standards for the free issuance of personal protective equipment in accordance with the appendix to this Instruction.
5. Shift logs (statements) must be kept in the boiler room to record operating parameters technical devices, the results of their inspection and testing, work performed during the shift, identified defects during the operation of the boilers.
6. To avoid fires and explosions of boilers, it is prohibited to work with faulty water indicators, pressure gauges, feeding devices, fittings, safety valves, safety automatics and emergency protection and alarm systems.
7. Disabling the automatic boiler safety system is prohibited. All cases of shutdown of the boiler safety automatics must be recorded in the shift log.
8. The driver (stoker) of the boiler room while on duty should not be distracted from performing the duties assigned to him by the instructions.
9. Persons who are not related to the operation of boilers and boiler room equipment should not be allowed into the boiler room. In necessary cases, unauthorized persons may be allowed into the boiler room only with the permission of its owner and accompanied by his representative (responsible for the good condition and safe operation of the boilers and others).
10. The premises, boilers and all boiler room equipment must be kept in good condition and proper cleanliness.
11. It is forbidden to clutter boiler room any materials or objects and store them on boilers and platforms. Passages in the boiler room and exits from it must always be free.
12. For violation of the requirements of these Instructions, the driver (stoker) of the boiler room is liable in accordance with the legislation of the Republic of Belarus.

OCCUPATIONAL SAFETY REQUIREMENTS BEFORE STARTING WORK

13. Before starting work you should:
check the serviceability and put on the personal protective equipment necessary for safe work. Contaminated or faulty personal protective equipment should be replaced;
inspect the workplace and remove everything that may interfere with work, clear the passages and do not block them.
14. When working in shifts, the shift must be accepted in accordance with the requirements of the internal labor regulations and recorded as an entry in the journal indicating the condition of the boiler, fittings and boiler room equipment.
15. The person handing over the shift must inform the driver (fireman) of the boiler room taking over the shift about all malfunctions noticed during work.
16. Before starting work you must:
carry out an external inspection of the boiler and equipment;
check the tightness and ease of opening and closing valves, drain valves, water level in boilers;
check the condition of water indicating devices, pressure gauges, feeding devices, fittings, safety valves, safety automatics and emergency protection and alarm systems;
check the illumination of the workplace, including instrumentation, the presence and serviceability of working tools, emergency lighting, portable electric lamps.
17. You should make sure that fire protection equipment is available and in working order, that the necessary equipment is available and complete medicines and medical products, first aid kits.
18. About identified violations of labor protection requirements that the driver (fireman) of the boiler room cannot eliminate on his own, he must report to his immediate supervisor in order to take measures to eliminate them.

LABOR SAFETY REQUIREMENTS WHEN PERFORMING WORK

19. When performing work, careful monitoring of the boiler room equipment should be carried out by inspecting it, checking the proper operation of fittings, control measuring instruments, safety valves, alarm and protection equipment, and feed pumps. A shift log should be maintained to record the results of inspection and testing.
20. You should check: the water level in the steam boiler, not allowing it to drop below the limit; pressure in the boiler, maintaining it within the permitted limits, marked on the pressure gauge with a red line; the water temperature in the hot water boiler and system, maintaining it within the specified range.
21. Inspection of water indicator valves, pressure gauges and safety valves should be carried out within the time limits established by the instructions on boiler operation (but at least once per shift).
22. The serviceability of the pressure gauge is checked using a three-way valve or shut-off valves that replace it by setting the pressure gauge needle to zero:

In addition to the specified check, the working pressure gauges should be checked at least once every 6 months with a control working pressure gauge that has the same scale and accuracy class as the pressure gauge being checked, with the results recorded in the control check log.
At least once every 12 months, pressure gauges must be verified with a stamp or seal installed in the manner prescribed by the State Standard of the Republic of Belarus.
23. Checking the water level indicators is carried out by blowing them. The serviceability of reduced level indicators is checked by comparing their readings with the readings of direct-acting water level indicators. The inspection must be carried out within the following time frames:
for boilers with operating pressure up to 1.4 MPa (14 bar) inclusive - at least once per shift;
for boilers with operating pressure over 1.4 MPa (14 bar) up to 4 MPa (40 bar) inclusive - at least once a day (except for boilers installed at thermal power plants);
for boilers with operating pressure over 4 MPa (40 bar) - in accordance with the schedule approved by the chief engineer.
24. The serviceability of safety valves is checked by forced short-term “explosion” of them within the following periods:
for boilers with operating pressure up to 1.4 MPa (14 bar) inclusive - at least once per shift;
for boilers with operating pressure over 1.4 MPa (14 bar) up to 4 MPa (40 bar) inclusive - at least once a day (except for boilers installed at thermal power plants);
for boilers with operating pressure over 4 MPa (40 bar) - in accordance with the schedule approved by the chief engineer.
25. The serviceability of backup feed, network make-up and other pumps is checked by briefly putting them into operation in accordance with the schedule approved by the chief engineer, but at least once a month.
26. Checking the serviceability of the alarm and automatic protection must be carried out in accordance with the schedule and instructions approved by the chief engineer of the organization.
27. The date, time and results of the above checks must be entered in the shift log signed by the person who carried out these checks.
28. Uniform combustion of solid fuel should be ensured over the entire area of ​​the grate, feeding it evenly in small portions with weakened blast; when the boiler load increases, it is necessary to first increase the draft, then increase the blast, and if the load decreases, first reduce the blast, then the draft; Clean the firebox regularly, every 4–5 hours; If the blower stops, you should immediately open the ash door to avoid burning the grate.
29. Stop the boiler in all cases, except emergency stop, should be carried out only by written order of the boiler room management.
30. Stopping a solid fuel boiler should be done in the following order: burn the remaining fuel in the furnace with reduced blast and draft, stop blasting and reduce draft: clean the furnace and stop draft; make sure the pressure drops to zero. It is forbidden to extinguish fuel in the firebox by filling it with water.
31. During boiler operation, it is prohibited:
carry out any work to repair its elements under pressure;
leave the boiler without constant supervision both during operation of the boiler and after it is stopped until the pressure in it decreases to atmospheric pressure and the water temperature reaches 30 °C.
32. Cleaning of the furnace should be carried out at reduced boiler load, weakened or switched off blast and reduced draft.
33. Slag and ash removed from the furnace are filled with water. Exhaust ventilation is turned on in the room above the place where they are poured.

OCCUPATIONAL SAFETY REQUIREMENTS AFTER WORK COMPLETION

34. The driver (fireman) of the boiler room at the end of the shift is obliged to hand over the boiler installation in complete cleanliness and order. Before leaving your shift, you must make sure that the slag and ash in the bunker or storage area are extinguished.
35. The driver (stoker) of the boiler room taking over the shift must write down in the shift log all the faults he discovered upon entering the shift and sign in the log together with the driver (stoker) of the boiler room handing over the shift.
36. In the event of detection of defects and malfunctions that impede the further safe operation of the boiler, the driver (fireman) taking over the shift is obliged to immediately notify the boiler room management about this.
37. It is prohibited to accept and hand over a shift during the liquidation of an accident and during critical switching operations.
38. Upon completion of all work, you should:
remove and put in order special clothing and other personal protective equipment, put them in the designated place for storage, and, if necessary, hand them over for washing (dry cleaning) or repair;
wash your hands and face with warm water and soap or similar detergents (it is not allowed to use substances not intended for this purpose for washing), if possible, take a shower.

OCCUPATIONAL SAFETY REQUIREMENTS IN EMERGENCIES

39. An emergency stop of the boiler must be carried out immediately in the following cases:
fault detection safety valve;
if the pressure in the boiler drum has risen above the permitted value by 10% and continues to rise;
reducing the water level below the lowest permissible level, in this case replenishing the boiler with water is prohibited;
increasing the water level above the highest permissible level;
stopping all feed pumps;
termination of all direct action water level indicators;
if cracks, bulges, or gaps in their welds, breakage of the anchor bolt or connection;
unacceptable increase or decrease in pressure in the direct-flow boiler path up to the built-in valves;
extinguishing of torches in the furnace during chamber combustion of fuel;
reducing water flow through the hot water boiler below the minimum permissible value;
reducing the water pressure in the hot water boiler circuit below the permissible level;
increasing the water temperature at the outlet of the hot water boiler to a value 20 °C below the saturation temperature corresponding to the operating water pressure in the boiler outlet manifold;
malfunction of safety or alarm systems, including loss of voltage to these devices;
the occurrence of a fire in the boiler room that threatens operating personnel or the boiler.
40. Emergency shutdown of the boiler must be carried out in the manner specified in the production instructions. The cause and time of emergency shutdown of the boiler must be recorded in the shift log, indicating the date and time (hours, minutes).
41. If a fire occurs, it is necessary to stop the boilers, call the emergency department by calling “101”, and report the incident to your immediate supervisor;
start extinguishing the fire using available means.
42. In case of an accident at work, you must:
quickly take measures to prevent the victim from being exposed to traumatic factors, provide first aid to the victim, call medical workers to the scene of the incident or deliver the victim to a healthcare organization;
report the incident to the work manager;
ensure the safety of the situation at the scene of the incident before the start of the investigation, and if this is not possible (there is a threat to the life and health of others, stopping continuous production) - record the situation by drawing up a diagram, protocol, photography or other method.
43. In all cases of injury or sudden illness, it is necessary to call medical workers to the scene of the incident, and if this is not possible, take the victim to the nearest health care organization.

Head ______________ Full name

AGREED:

occupational safety engineer

Full name

"___" __________201_

Application

to Sample instructions

on labor protection for the driver (fireman) of the boiler room

Personal protective equipment provided for by standard standards

for the driver (fireman) of the boiler room

Profession code according to OKRB 006-2009

Name

professions,

positions

Name

personal protective equipment

Classification (labeling) of personal protective equipment according to protective properties

Wearing period

in months

13786 Boiler room operator (fireman)Cotton suit
Cotton hat
Leather boots
Combined mittens

Before wear

Safety glasses

Before wear

When working in a boiler room operating on liquid fuel, additionally:

oil- and fat-protective rubber ankle boots

When manually loading solid fuel boilers:

half-linen canvas suit with fire-retardant trim
half-linen canvas headdress with fire-retardant trim
leather boots (tarpaulin boots)
canvas mittens

Before wear

safety glasses

Before wear

In winter, for outdoor work additionally:

protective suit low temperatures made of cotton fabric
felted shoes
galoshes for felted shoes

"I affirm"

Director

Municipal educational institution "Lozhinskaya main

secondary school"

_____________

09/01/2010

OFFICIAL

INSTRUCTIONS

STOKER

1. General provisions

1.1. This job description has been developed on the basis of the tariff and qualification characteristics for the industry-wide profession of the worker “stoker”.
1.2. A fireman is hired and dismissed by the school director on the recommendation of the school’s deputy director for administrative and economic work, without presenting requirements for education and work experience.
1.3. The fireman reports directly to the deputy school director for administrative and economic work (supervisor).
1.4. In his work, the fireman is guided by the rules and instructions for the protection of buildings and structures; general rules and standards of labor protection, industrial sanitation and fire protection, as well as the Charter and Internal Labor Regulations of the school and these Instructions.

2. Functions

The main purpose of the position of a stoker is to heat buildings and structures during scheduled and after-hours hours.

3. Job responsibilities

The fireman performs the following duties:
3.1. checks the integrity of the heating system and the availability of fire-fighting equipment; serviceability of alarms, telephones, lighting together with a representative of the administration or a replacement fireman;
3.2. makes external and internal rounds heating system, checking the quality of heat supplied to classrooms and school premises (at least three times per shift);
3.3. when identifying malfunctions in the heating system, reports this to the person to whom he is subordinate, a representative of the administration;
3.4. if a fire occurs at the facility, raises the alarm, notifies the fire brigade and the police officer on duty, and takes measures to extinguish the fire;
3.5. carries out reception and delivery of duty, with the corresponding entry in the journal;
3.6. complies with safety rules when servicing electrical appliances.
3.7. The employee is obliged to comply with the requirements of the internal regulations:
- maintain discipline;
- treat equipment, tools, instruments, materials, and workwear with care;
- keep the workplace clean;
- undergo periodic medical examinations.
3.8. The consumption of alcoholic beverages and drugs is not permitted in the workplace.
3.9. Follow fire safety rules.
3.10. Maintain personal hygiene rules
3.11. For violation of the instructions, the employee is held accountable.

The watchman has the right:
4.1. for the allocation and equipment of a special room;
4.2. to receive special clothing according to established standards;
4.3. refuse assigned work if a situation arises that is dangerous for
surrounding people and his health.

5. Responsibility

5.1. In boiler rooms it is PROHIBITED:
a) CARRY out work not related to the operation of the boiler room;
b) allow into the boiler room and entrust supervision of the operation of motors and boilers
to unauthorized persons;
c) ignite boiler installations without first purging them with air;
d) leave boilers in operation unattended;
e) do not allow persons who have not received special training to work, and also
persons who were intoxicated;
f) store reserves of solid fuel exceeding the daily requirement;
g) light stoves with kerosene;
h) heat stoves with faulty and open doors, as well as use
for burning firewood longer than the depth of the firebox
i) remove glass covers from indoor lighting fixtures.
5.2. For non-fulfillment or improper fulfillment without good reason of the internal labor regulations of the school, legal orders and instructions of the school administration and other local regulations, job responsibilities established by these Instructions, the fireman bears disciplinary liability in the manner prescribed by labor legislation.
5.3. For culpable infliction of damage to the school or participants in the educational process in connection with the performance (non-performance) of their official duties, the fireman bears financial liability in the manner and within the limits established by labor and (or) civil legislation.

6. Relationships. Relationships by position

Fireman:
6.1. works in a normal working day (without the right to sleep) according to a schedule drawn up based on a 40-hour work week and approved by the school director on the proposal of the deputy director of the school for administrative and economic work of the caretaker);
6.2. undergoes safety and fire safety training under the guidance of the school’s deputy director for administrative and economic work (supply manager).